Start with the building. Then size the system.

Hydronic design is about matching the heat source, water temperatures, hydraulic circuit, indoor emitters and controls to the actual building load.

Design process

Good hydronic design starts before equipment selection.

The first questions are not “which heat pump?” They are “what does the building need?” and “how will that energy be delivered?”

1Establish heating and cooling loads.
2Determine domestic hot-water demand where applicable.
3Select room-side emitters and operating temperatures.
4Design the hydraulic circuits, pumps, valves and controls.
5Select and size the heat pump and storage.

Typical water-temperature ranges

Fan coils: approximately 35–45°C for heating in the EVOHX technical material.

Radiators / towel rails: approximately 45–55°C in the same material.

Actual design temperatures depend on emitter selection, heat loss, comfort requirements and manufacturer data.

Hydraulic architecture

One loop or several?

The building determines the architecture. A small home and a multi-storey apartment building may use very different hydraulic arrangements.

Standalone

A smaller system can serve one dwelling with heating, cooling and domestic hot water from one outdoor heat-pump platform.

Central two-pipe

A central system can distribute water for heating or cooling and use a separate DHW service. The central space-conditioning mode is one at a time.

Four-pipe

Separate heating and cooling circuits can allow simultaneous heating and cooling, but this adds plant, controls and hydraulic complexity.

Domestic hot water

Storage is part of the design.

DHW storage should be selected from actual demand rather than simply choosing a tank size from a catalogue. Peak usage, recovery time, ring-main requirements and available plant space all matter.

EVOHX technical material identifies 300–500 litre storage as a typical range for one central arrangement, but project sizing must be confirmed from demand.

Design itemWhy it matters
Heat loadDetermines required heating capacity.
Cooling loadDetermines summer capacity and condensate requirements.
Water temperatureInfluences emitter output and heat-pump performance.
DHW demandDetermines storage and recovery requirements.
HydraulicsDetermines flow, pressure loss, pump and pipe sizing.
Design support

Bring us the building information.

Plans, floor areas, room use, heat-load information, emitter preferences and hot-water requirements give us the information needed to discuss a system properly.

Send project information